2 FIELDBUSINSTALLATION
2.1 GENERAL
FLOWBUSis a 3wire,RS485basedfield buscommunicationsystemfor parameter valueexchangebetweendigital
Bronkhorstproducts.Inthissystemeachinstrument/deviceisequippedwithamicrocontrollerforitsowndedicated
task but also for exchanging parameter value information with other instruments /devices connected to the sam
e
FLOWBUSsystem.
FLOWBUSsystemsmayhaveaminimumof2andamaximumof126connections.Themaximumlengthfordatelines
between the first and the last connection may be up to approx. 600 meters. Longer distances are only possible in
combination with special busrepeater m
odules. Each instrument/device connection Tpart (stub) must be kept as
shortaspossible(maximumcablelength0.5meter).
Thebaudrateusedtotransportmessagesis187500baudor400000*baud.
FLOWBUSisamultimasternetworkwithatokenringarchitecture.
*MBC3typeinstrumentshaveanadditionalbaudrateavailableof400000baud.