Bronkhorst FLOW-BUS interface User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 26
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
BRONKHORST®
2 FIELDBUSINSTALLATION
2.1 GENERAL
FLOW‐BUSis a 3‐wire,RS485‐basedfield buscommunicationsystemfor parameter valueexchangebetweendigital
Bronkhorstproducts.Inthissystemeachinstrument/deviceisequippedwithamicro‐controllerforitsowndedicated
task but also for exchanging parameter value information with other instruments /devices connected to the sam
e
FLOW‐BUSsystem.
FLOW‐BUSsystemsmayhaveaminimumof2andamaximumof126connections.Themaximumlengthfordatelines
between the first and the last connection may be up to approx. 600 meters. Longer distances are only possible in
combination with special bus‐repeater m
odules. Each instrument/device connection T‐part (stub) must be kept as
shortaspossible(maximumcablelength0.5meter).
Thebaudrateusedtotransportmessagesis187500baudor400000*baud.
FLOW‐BUSisamulti‐masternetworkwithatoken‐ringarchitecture.
*MBC3typeinstrumentshaveanadditionalbaudrateavailableof400000baud.
Page11
FLOW‐BUSinterface9.17.024
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 25 26

Comments to this Manuals

No comments