1.4 SHORTFORMSTARTUP
AllnecessarysettingsforthismodulearealreadyperformedatBronkhorst.
TofollownextstepscarefullyisthequickestwaytogetthismoduleoperationalinyourownDeviceNetenvironment.
START
Master
present
LoadEDS
MakesureyourmasterhasbeeninstalledtotheDeviceNetsystem
LoadEDSfilewithconfigurationtool
Copybitmaps
Bitmaps(withflowcontrollers)canbecopiedintheproperdirectory(mostly
automatic,sometimesbyhand;dependsonprogram)
AddslavetoDeviceNet
system
Select"Bronkhorstmeter/controller"andaddnewinstrumenttothebus
Setdeviceconfiguration
Setparameterdata
Setparameterdataforacyclicsettingofparametervalues
SetMACIDandbaudrate
ofinstrument:
Defaultinstrumentswillbedeliveredtocustomersonaddress63andwitha
baudrateof125000baud.Normallysettinganaddresscanbeperformedby
yourmasterconfigurationsoftware.
However,ifyouchoosetosetastationaddressofflineyoucan
usethe
programmeFLOWFIXtochangeMACIDandbaudrateviaRS232
connection.MACIDandbaudratecanalsobechangedbyusingthebutton
ontopoftheinstrumentortherotaryswitchesonthesideofthe
instrumentifpresent.Seechapter8formoredetails.
Downloadconfiguration
Downloadallconfigurationsettingsintoyourmaster
Testdataexchange
Testdataexchangecommunicationbetweenyourmasterandthe
instrument(s)
Ready