BRONKHORST CORI-TECH B.V.
7 TROUBLESHOOTING
7.1 General
For a correct analysis of the proper operation of a CORI-FLOW meter or controller it is recommended to
remove the unit from the process line and check it without applying fluid supply pressure. In case the unit is
dirty, this can be ascertained immediately by loosening the compression type couplings and, if applicable the
flange on the inlet side.
Furthermore remove the two covers and check if all connectors are fixed properly. Energising or de-
energising of the instrument indicates whether there is an electronic failure. When powering up the red LED
is on and the green LED is flashing for a second or two. Then the instrument should go in normal operation
mode. See document number 9.17.023 for detailed description of the LED indication.
After that, fluid pressure is to be applied in order to check behaviour.
7.2 Troubleshooting summary general
1b) check cable connection
Output stage blown-up due to long lasting
shortage and/or high-voltage peaks
Supply pressure too low, or differential pressure
across meter too low
1d) increase supply pressure
Valve blocked/contaminated
1e) connect 0 .. 15 Vdc to valve and slowly
increase voltage while supply pressure is ‘on’.
The valve should open at 7V ± 3V; if not open,
then clean parts and adjust valve (qualified
Screen in inlet fitting blocked
Output signal much lower than
setpoint signal or desired flow
Screen blocked/contamined
sensor blocked/contaminated
3b) clean sensor with a gas or fluid
Valve blocked/contaminated
Valve internal damage (swollen seat in plunger)
3d) replace plunger assembly and adjust valve
or return
Incorrect type of gas is used and/or pressure/diff.
pressure is to low
3e) try instrument on conditions for which it was
designed
Flow is gradually decreasing
Condensation, occurs with
, hydrocarbons
such as
etc.
4a) decrease supply pressure and/or heat gas
to be measured
Valve adjustment has changed
Supply pressure/diff. pressure too high
Pipeline too short between pressure regulator
and Cori-Flow
5b) increase length or diameter of piping
upstream
External vibration is present
5c) Remove external vibration
Valve sleeve or internals damaged
5d) replace damaged parts and adjust valve,
see ‘1e’ or return to factory
Controller adjustment wrong
Software like FLOWPLOT can be used to do
this. Please contact the distributor for details.
Small flow at zero setpoint
Valve leaks due to damaged plunger or dirt in
orifice
6a) clean orifice and/or, when replacing plunger
assembly, see ‘1e’
Pressure too high or much too low
6b) apply correct pressure
High flow at zero setpoint
Damaged diaphragm (only applicable to valves
with membrane)
7a) replace membrane seal
Expansion of liquids to gasses
8b) Check properties fluid used
9c) Measure long enough to get a reliable
measurement
Right reference instrument
9d) The Cori-Flow is a mass-flow
meter/controller and should not be checked with
Note: For other (more specific) problems see also troubleshooting parts in other documents.
page 26 9.17.031
Comments to this Manuals